AUTROL ATT2100 SMART TEMPERATURE TRANSMITTER

Mã sản phẩm: AUTROL ATT2100

Giá: Liên hệ

Feature 4 to 20mA, HART, Loop Powered, Digital Accuracy: RTD ±0.17 ℃ , T/C ±0.77 ℃, 3 lines LCD display, Self Diagnostic Function

Mô tả sản phẩm

AUTROL ATT2100 SMART TEMPERATURE TRANSMITTER

ĐỒNG HỒ ĐO NHIỆT ĐỘ AUTROL ATT2100

AUTROL TEMPERATURE ATT2100

FUNCTION: AUTROL ATT2100

  • Type Temperature Transmitter(TIT), Field Mounting Type
  • Certificate Ex d, FM, ATEX, TR CU(EAC), CE, KCs, IP66/67.
  • Feature 4 to 20mA, HART, Loop Powered, Digital Accuracy: RTD ±0.17 ℃ , T/C ±0.77 ℃, 3 lines LCD display, Self Diagnostic Function,
  • External Buttons, DAC, Zero Trim, Eng mode
  • Input RTD input: a=0.00385(KS, JIS, DIN, IEC), a=0.00391(US), Thermocouple input: KSC 1602-1982, JISC 1602-1981, ANSI MC96.1-1982, Millivolt, ohms
  • Application Pressure, Flow, Level measurement for Oil & Gas, Liquid, Water, Maine & offshore, Vessel, Power, Chemical Plants and Refinary

SPECIFICATION: AUTROL ATT2100

  • Model Name ATT2100
  • Protocol Digital Communication, HART 5, 7 Trim ability Zero, DAC
  • Power supply & Load Requirement 250 to 550 ohm @ 24 Vdc, Loop Powered Falure Mode Low ≤ 3.78 mA, High ≥ 21.1 mA
  • External Buttons Zero & Span 2 buttons for device configuration
  • Ambient Temp. limit -40 to 85℃ ( -104 to 185℉ )
  • Stability RTD – 2 years (±0.12% of Reading or 0.15℃ whichever is greater),
    T/C – 1 years (±0.12% of Reading or 0.15℃ whichever is greater)

Tài liệu tham khảo:

Các tên gọi liên quan: MÁY PHÁT NHIỆT ĐỘ THÔNG MINH AUTROL ATT2100, BỘ ĐIỀU KHIỂN NHIỆT ĐỘ AUTROL ATT2100, BỘ CHUYỂN ĐỔI NHIỆT ĐỘ AUTROL ATT2100, ĐỒNG HỒ ĐO NHIỆT ĐỘ AUTROL ATT2100, THIẾT BỊ ĐO NHIỆT ĐỘ AUTROL ATT2100

 

Type

 

Ex Field mount

 

Din Rail mount

 

Head mount

 

Input

 

RTD (2, 3, 4 wires, a=0.00385), T/C (B, E, J, K, N, R, S, T), mV, ohm

 

 

Feature

 

4 to 20mA, Digital Signals, Loop Powered, HART 5, 7

 

RTD Stability for 24 months (+/- 0.12 % of reading or 0.15 degC whichever is greater)

 

Certificate

 

Ex d, FM, ATEX, DNV, KCs

 

 

Ex ia, ATEX

 

Span

 

RTD : -200 to 650 deg C , T/C : - 200 to 1820 deg C

 

Accuracy

Digital/ Analogue Accuracy of SPAN ( +/- 0.03%) + (Digital Accuracy / SPAN x 100) Digital Accuracy - RTD : max +/- 0.17 deg C , T/C : max +/- 0.77 deg C

 

Ambient Temp.

 

-40 to 85 deg C

 

Points Features

External Buttons, 3 lines LCD display, Failure Mode, Trim, Unit changeable

 

Self Diagnostic Function

 

Universal size, Ex ia